CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2022-38371 1 Siemens 39 Apogee Modular Building Controller, Apogee Modular Building Controller Firmware, Apogee Modular Equiment Controller and 36 more 2024-05-14 N/A 7.5 HIGH
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), Desigo PXC00-E.D (All versions >= V2.3), Desigo PXC00-U (All versions >= V2.3), Desigo PXC001-E.D (All versions >= V2.3), Desigo PXC100-E.D (All versions >= V2.3), Desigo PXC12-E.D (All versions >= V2.3), Desigo PXC128-U (All versions >= V2.3), Desigo PXC200-E.D (All versions >= V2.3), Desigo PXC22-E.D (All versions >= V2.3), Desigo PXC22.1-E.D (All versions >= V2.3), Desigo PXC36.1-E.D (All versions >= V2.3), Desigo PXC50-E.D (All versions >= V2.3), Desigo PXC64-U (All versions >= V2.3), Desigo PXM20-E (All versions >= V2.3), Nucleus NET for Nucleus PLUS V1 (All versions < V5.2a), Nucleus NET for Nucleus PLUS V2 (All versions < V5.4), Nucleus ReadyStart V3 V2012 (All versions < V2012.08.1), Nucleus ReadyStart V3 V2017 (All versions < V2017.02.4), Nucleus Source Code (All versions including affected FTP server), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The FTP server does not properly release memory resources that were reserved for incomplete connection attempts by FTP clients. This could allow a remote attacker to generate a denial of service condition on devices that incorporate a vulnerable version of the FTP server.
CVE-2019-13939 1 Siemens 46 Apogee Modular Building Controller, Apogee Modular Building Controller Firmware, Apogee Modular Equiment Controller and 43 more 2024-02-13 4.8 MEDIUM 7.1 HIGH
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus Source Code (All versions). By sending specially crafted DHCP packets to a device where the DHCP client is enabled, an attacker could change the IP address of the device to an invalid value.
CVE-2021-31884 1 Siemens 42 Apogee Modular Building Controller, Apogee Modular Building Controller Firmware, Apogee Modular Equiment Controller and 39 more 2023-06-26 7.5 HIGH 9.8 CRITICAL
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.4), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.19), APOGEE PXC Modular (BACnet) (All versions < V3.5.4), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.19), Capital VSTAR (All versions with enabled Ethernet options), Desigo PXC00-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC00-U (All versions >= V2.3 and < V6.30.016), Desigo PXC001-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC100-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC12-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC128-U (All versions >= V2.3 and < V6.30.016), Desigo PXC200-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC36.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC50-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC64-U (All versions >= V2.3 and < V6.30.016), Desigo PXM20-E (All versions >= V2.3 and < V6.30.016), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus Source Code (All versions), TALON TC Compact (BACnet) (All versions < V3.5.4), TALON TC Modular (BACnet) (All versions < V3.5.4). The DHCP client application assumes that the data supplied with the “Hostname” DHCP option is NULL terminated. In cases when global hostname variable is not defined, this may lead to Out-of-bound reads, writes, and Denial-of-service conditions. (FSMD-2021-0014)
CVE-2021-31888 1 Siemens 41 Apogee Modular Building Controller, Apogee Modular Building Controller Firmware, Apogee Modular Equiment Controller and 38 more 2023-05-16 6.5 MEDIUM 8.8 HIGH
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.4), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.19), APOGEE PXC Modular (BACnet) (All versions < V3.5.4), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.19), Desigo PXC00-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC00-U (All versions >= V2.3 and < V6.30.016), Desigo PXC001-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC100-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC12-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC128-U (All versions >= V2.3 and < V6.30.016), Desigo PXC200-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC36.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC50-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC64-U (All versions >= V2.3 and < V6.30.016), Desigo PXM20-E (All versions >= V2.3 and < V6.30.016), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus Source Code (All versions), TALON TC Compact (BACnet) (All versions < V3.5.4), TALON TC Modular (BACnet) (All versions < V3.5.4). FTP server does not properly validate the length of the “MKD/XMKD” command, leading to stack-based buffer overflows. This may result in Denial-of-Service conditions and Remote Code Execution. (FSMD-2021-0018)
CVE-2021-31887 1 Siemens 41 Apogee Modular Building Controller, Apogee Modular Building Controller Firmware, Apogee Modular Equiment Controller and 38 more 2023-03-13 6.5 MEDIUM 8.8 HIGH
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.4), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.19), APOGEE PXC Modular (BACnet) (All versions < V3.5.4), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.19), Desigo PXC00-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC00-U (All versions >= V2.3 and < V6.30.016), Desigo PXC001-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC100-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC12-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC128-U (All versions >= V2.3 and < V6.30.016), Desigo PXC200-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC36.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC50-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC64-U (All versions >= V2.3 and < V6.30.016), Desigo PXM20-E (All versions >= V2.3 and < V6.30.016), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus Source Code (All versions), TALON TC Compact (BACnet) (All versions < V3.5.4), TALON TC Modular (BACnet) (All versions < V3.5.4). FTP server does not properly validate the length of the “PWD/XPWD” command, leading to stack-based buffer overflows. This may result in Denial-of-Service conditions and Remote Code Execution. (FSMD-2021-0016)
CVE-2021-31886 1 Siemens 41 Apogee Modular Building Controller, Apogee Modular Building Controller Firmware, Apogee Modular Equiment Controller and 38 more 2023-02-10 7.5 HIGH 9.8 CRITICAL
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.4), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.19), APOGEE PXC Modular (BACnet) (All versions < V3.5.4), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.19), Desigo PXC00-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC00-U (All versions >= V2.3 and < V6.30.016), Desigo PXC001-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC100-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC12-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC128-U (All versions >= V2.3 and < V6.30.016), Desigo PXC200-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC36.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC50-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC64-U (All versions >= V2.3 and < V6.30.016), Desigo PXM20-E (All versions >= V2.3 and < V6.30.016), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus Source Code (All versions), TALON TC Compact (BACnet) (All versions < V3.5.4), TALON TC Modular (BACnet) (All versions < V3.5.4). FTP server does not properly validate the length of the “USER” command, leading to stack-based buffer overflows. This may result in Denial-of-Service conditions and Remote Code Execution. (FSMD-2021-0010)