Vulnerabilities (CVE)

Filtered by vendor Siemens Subscribe
Total 1761 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2023-44374 1 Siemens 142 6ag1206-2bb00-7ac2, 6ag1206-2bb00-7ac2 Firmware, 6ag1206-2bs00-7ac2 and 139 more 2024-06-11 N/A 8.8 HIGH
Affected devices allow to change the password, but insufficiently check which password is to be changed. With this an authenticated attacker could, under certain conditions, be able to change the password of another, potential admin user allowing her to escalate her privileges.
CVE-2023-44373 1 Siemens 142 6ag1206-2bb00-7ac2, 6ag1206-2bb00-7ac2 Firmware, 6ag1206-2bs00-7ac2 and 139 more 2024-06-11 N/A 9.1 CRITICAL
Affected devices do not properly sanitize an input field. This could allow an authenticated remote attacker with administrative privileges to inject code or spawn a system root shell. Follow-up of CVE-2022-36323.
CVE-2023-44319 1 Siemens 142 6ag1206-2bb00-7ac2, 6ag1206-2bb00-7ac2 Firmware, 6ag1206-2bs00-7ac2 and 139 more 2024-06-11 N/A 4.9 MEDIUM
Affected devices use a weak checksum algorithm to protect the configuration backup that an administrator can export from the device. This could allow an authenticated attacker with administrative privileges or an attacker that tricks a legitimate administrator to upload a modified configuration file to change the configuration of an affected device.
CVE-2023-44318 1 Siemens 142 6ag1206-2bb00-7ac2, 6ag1206-2bb00-7ac2 Firmware, 6ag1206-2bs00-7ac2 and 139 more 2024-06-11 N/A 4.9 MEDIUM
Affected devices use a hardcoded key to obfuscate the configuration backup that an administrator can export from the device. This could allow an authenticated attacker with administrative privileges or an attacker that obtains a configuration backup to extract configuration information from the exported file.
CVE-2023-44317 1 Siemens 138 Scalance Xb205-3 \(sc\, Pn\), Scalance Xb205-3 \(sc\, Pn\) Firmware, Scalance Xb205-3 \(st\, E\/ip\) and 135 more 2024-06-11 N/A 7.2 HIGH
Affected products do not properly validate the content of uploaded X509 certificates which could allow an attacker with administrative privileges to execute arbitrary code on the device.
CVE-2023-38640 1 Siemens 1 Sicam Pas\/pqs 2024-06-11 N/A 4.4 MEDIUM
A vulnerability has been identified in SICAM PAS/PQS (All versions >= V8.00 < V8.22). The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to read and modify configuration data in the context of the application process.
CVE-2022-46144 1 Siemens 12 6gk5622-2gs00-2ac2, 6gk5622-2gs00-2ac2 Firmware, 6gk5626-2gs00-2ac2 and 9 more 2024-06-11 N/A 6.5 MEDIUM
A vulnerability has been identified in SCALANCE SC622-2C (6GK5622-2GS00-2AC2) (All versions < V2.3), SCALANCE SC622-2C (6GK5622-2GS00-2AC2) (All versions >= V2.3 < V3.0), SCALANCE SC626-2C (6GK5626-2GS00-2AC2) (All versions < V2.3), SCALANCE SC626-2C (6GK5626-2GS00-2AC2) (All versions >= V2.3 < V3.0), SCALANCE SC632-2C (6GK5632-2GS00-2AC2) (All versions < V2.3), SCALANCE SC632-2C (6GK5632-2GS00-2AC2) (All versions >= V2.3 < V3.0), SCALANCE SC636-2C (6GK5636-2GS00-2AC2) (All versions < V2.3), SCALANCE SC636-2C (6GK5636-2GS00-2AC2) (All versions >= V2.3 < V3.0), SCALANCE SC642-2C (6GK5642-2GS00-2AC2) (All versions < V2.3), SCALANCE SC642-2C (6GK5642-2GS00-2AC2) (All versions >= V2.3 < V3.0), SCALANCE SC646-2C (6GK5646-2GS00-2AC2) (All versions < V2.3), SCALANCE SC646-2C (6GK5646-2GS00-2AC2) (All versions >= V2.3 < V3.0), SCALANCE WAM763-1 (6GK5763-1AL00-7DA0) (All versions), SCALANCE WAM763-1 (ME) (6GK5763-1AL00-7DC0) (All versions), SCALANCE WAM763-1 (US) (6GK5763-1AL00-7DB0) (All versions), SCALANCE WAM766-1 (EU) (6GK5766-1GE00-7DA0) (All versions), SCALANCE WAM766-1 (ME) (6GK5766-1GE00-7DC0) (All versions), SCALANCE WAM766-1 (US) (6GK5766-1GE00-7DB0) (All versions), SCALANCE WAM766-1 EEC (EU) (6GK5766-1GE00-7TA0) (All versions), SCALANCE WAM766-1 EEC (ME) (6GK5766-1GE00-7TC0) (All versions), SCALANCE WAM766-1 EEC (US) (6GK5766-1GE00-7TB0) (All versions), SCALANCE WUM763-1 (6GK5763-1AL00-3AA0) (All versions), SCALANCE WUM763-1 (6GK5763-1AL00-3DA0) (All versions), SCALANCE WUM763-1 (US) (6GK5763-1AL00-3AB0) (All versions), SCALANCE WUM763-1 (US) (6GK5763-1AL00-3DB0) (All versions), SCALANCE WUM766-1 (EU) (6GK5766-1GE00-3DA0) (All versions), SCALANCE WUM766-1 (ME) (6GK5766-1GE00-3DC0) (All versions), SCALANCE WUM766-1 (US) (6GK5766-1GE00-3DB0) (All versions). Affected devices do not properly process CLI commands after a user forcefully quitted the SSH connection. This could allow an authenticated attacker to make the CLI via SSH or serial interface irresponsive.
CVE-2022-43768 1 Siemens 48 Simatic Cp 1242-7 V2, Simatic Cp 1242-7 V2 Firmware, Simatic Cp 1243-1 and 45 more 2024-06-11 N/A 7.5 HIGH
A vulnerability has been identified in SIMATIC CP 1242-7 V2 (6GK7242-7KX31-0XE0) (All versions), SIMATIC CP 1243-1 (6GK7243-1BX30-0XE0) (All versions), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions), SIMATIC CP 1243-7 LTE EU (6GK7243-7KX30-0XE0) (All versions), SIMATIC CP 1243-7 LTE US (6GK7243-7SX30-0XE0) (All versions), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions), SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE0) (All versions < V3.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE1) (All versions < V3.3), SIMATIC CP 443-1 Advanced (6GK7443-1GX30-0XE0) (All versions < V3.3), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS NET CP 1242-7 V2 (6AG1242-7KX31-7XE0) (All versions), SIPLUS NET CP 443-1 (6AG1443-1EX30-4XE0) (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (6AG1443-1GX30-4XE0) (All versions < V3.3), SIPLUS S7-1200 CP 1243-1 (6AG1243-1BX30-2AX0) (All versions), SIPLUS S7-1200 CP 1243-1 RAIL (6AG2243-1BX30-1XE0) (All versions), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.3.6), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.3.6). The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation of the webserver of the affected product.
CVE-2022-43767 1 Siemens 48 Simatic Cp 1242-7 V2, Simatic Cp 1242-7 V2 Firmware, Simatic Cp 1243-1 and 45 more 2024-06-11 N/A 7.5 HIGH
A vulnerability has been identified in SIMATIC CP 1242-7 V2 (6GK7242-7KX31-0XE0) (All versions), SIMATIC CP 1243-1 (6GK7243-1BX30-0XE0) (All versions), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions), SIMATIC CP 1243-7 LTE EU (6GK7243-7KX30-0XE0) (All versions), SIMATIC CP 1243-7 LTE US (6GK7243-7SX30-0XE0) (All versions), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions), SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE0) (All versions < V3.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE1) (All versions < V3.3), SIMATIC CP 443-1 Advanced (6GK7443-1GX30-0XE0) (All versions < V3.3), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS NET CP 1242-7 V2 (6AG1242-7KX31-7XE0) (All versions), SIPLUS NET CP 443-1 (6AG1443-1EX30-4XE0) (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (6AG1443-1GX30-4XE0) (All versions < V3.3), SIPLUS S7-1200 CP 1243-1 (6AG1243-1BX30-2AX0) (All versions), SIPLUS S7-1200 CP 1243-1 RAIL (6AG2243-1BX30-1XE0) (All versions), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.3.6), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.3.6). The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation of the webserver of the affected product.
CVE-2022-43716 1 Siemens 48 Simatic Cp 1242-7 V2, Simatic Cp 1242-7 V2 Firmware, Simatic Cp 1243-1 and 45 more 2024-06-11 N/A 7.5 HIGH
A vulnerability has been identified in SIMATIC CP 1242-7 V2 (6GK7242-7KX31-0XE0) (All versions), SIMATIC CP 1243-1 (6GK7243-1BX30-0XE0) (All versions), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions), SIMATIC CP 1243-7 LTE EU (6GK7243-7KX30-0XE0) (All versions), SIMATIC CP 1243-7 LTE US (6GK7243-7SX30-0XE0) (All versions), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions), SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE0) (All versions < V3.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE1) (All versions < V3.3), SIMATIC CP 443-1 Advanced (6GK7443-1GX30-0XE0) (All versions < V3.3), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS NET CP 1242-7 V2 (6AG1242-7KX31-7XE0) (All versions), SIPLUS NET CP 443-1 (6AG1443-1EX30-4XE0) (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (6AG1443-1GX30-4XE0) (All versions < V3.3), SIPLUS S7-1200 CP 1243-1 (6AG1243-1BX30-2AX0) (All versions), SIPLUS S7-1200 CP 1243-1 RAIL (6AG2243-1BX30-1XE0) (All versions), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.3.6), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.3.6). The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation which leads to a restart of the webserver of the affected product.
CVE-2022-38773 1 Siemens 140 Simatic Drive Controller Cpu 1504d Tf, Simatic Drive Controller Cpu 1504d Tf Firmware, Simatic Drive Controller Cpu 1507d Tf and 137 more 2024-06-11 N/A 6.8 MEDIUM
Affected devices do not contain an Immutable Root of Trust in Hardware. With this the integrity of the code executed on the device can not be validated during load-time. An attacker with physical access to the device could use this to replace the boot image of the device and execute arbitrary code.
CVE-2020-28400 1 Siemens 157 Dk Standard Ethernet Controller Evaluation Kit, Dk Standard Ethernet Controller Evaluation Kit Firmware, Ek-ertec 200 Evaulation Kit and 154 more 2024-06-11 5.0 MEDIUM 7.5 HIGH
Affected devices contain a vulnerability that allows an unauthenticated attacker to trigger a denial-of-service condition. The vulnerability can be triggered if a large amount of DCP reset packets are sent to the device.
CVE-2016-20009 2 Siemens, Windriver 15 Sgt-100, Sgt-100 Firmware, Sgt-200 and 12 more 2024-05-17 7.5 HIGH 9.8 CRITICAL
A DNS client stack-based buffer overflow in ipdnsc_decode_name() affects Wind River VxWorks 6.5 through 7. NOTE: This vulnerability only affects products that are no longer supported by the maintainer
CVE-2024-22039 1 Siemens 9 Cerberus Pro En Engineering Tool, Cerberus Pro En Fire Panel Fc72x, Cerberus Pro En X200 Cloud Distribution and 6 more 2024-05-14 N/A 9.8 CRITICAL
A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions < IP8), Cerberus PRO EN Fire Panel FC72x IP6 (All versions < IP6 SR3), Cerberus PRO EN Fire Panel FC72x IP7 (All versions < IP7 SR5), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions < V3.0.6602), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.0.5016), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions < V3.2.6601), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.2.5015), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions < MP8), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions < MP6 SR3), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions < MP7 SR5), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions < V3.0.6602), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.0.5016), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions < V3.2.6601), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.2.5015), Sinteso Mobile (All versions < V3.0.0). The network communication library in affected systems does not validate the length of certain X.509 certificate attributes which might result in a stack-based buffer overflow. This could allow an unauthenticated remote attacker to execute code on the underlying operating system with root privileges.
CVE-2023-46285 1 Siemens 4 Opcenter Quality, Simatic Pcs Neo, Sinumerik Integrate Runmyhmi \/automotive and 1 more 2024-05-14 N/A 7.5 HIGH
A vulnerability has been identified in Opcenter Quality (All versions < V2312), SIMATIC PCS neo (All versions < V4.1), SINEC NMS (All versions < V2.0 SP1), Totally Integrated Automation Portal (TIA Portal) V14 (All versions), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 7), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 3). The affected application contains an improper input validation vulnerability that could allow an attacker to bring the service into a Denial-of-Service state by sending a specifically crafted message to 4004/tcp. The corresponding service is auto-restarted after the crash is detected by a watchdog.
CVE-2023-46284 1 Siemens 4 Opcenter Quality, Simatic Pcs Neo, Sinumerik Integrate Runmyhmi \/automotive and 1 more 2024-05-14 N/A 7.5 HIGH
A vulnerability has been identified in Opcenter Quality (All versions < V2312), SIMATIC PCS neo (All versions < V4.1), SINEC NMS (All versions < V2.0 SP1), Totally Integrated Automation Portal (TIA Portal) V14 (All versions), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 7), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 3). The affected application contains an out of bounds write past the end of an allocated buffer when handling specific requests on port 4002/tcp and 4004/tcp. This could allow an attacker to crash the application. The corresponding service is auto-restarted after the crash.
CVE-2023-46283 1 Siemens 4 Opcenter Quality, Simatic Pcs Neo, Sinumerik Integrate Runmyhmi \/automotive and 1 more 2024-05-14 N/A 7.5 HIGH
A vulnerability has been identified in Opcenter Quality (All versions < V2312), SIMATIC PCS neo (All versions < V4.1), SINEC NMS (All versions < V2.0 SP1), Totally Integrated Automation Portal (TIA Portal) V14 (All versions), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 7), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 3). The affected application contains an out of bounds write past the end of an allocated buffer when handling specific requests on port 4002/tcp. This could allow an attacker to crash the application. The corresponding service is auto-restarted after the crash.
CVE-2023-46282 1 Siemens 4 Opcenter Quality, Simatic Pcs Neo, Sinumerik Integrate Runmyhmi \/automotive and 1 more 2024-05-14 N/A 6.1 MEDIUM
A vulnerability has been identified in Opcenter Quality (All versions < V2312), SIMATIC PCS neo (All versions < V4.1), SINEC NMS (All versions < V2.0 SP1), Totally Integrated Automation Portal (TIA Portal) V14 (All versions), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 7), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 3). A reflected cross-site scripting (XSS) vulnerability exists in the web interface of the affected applications that could allow an attacker to inject arbitrary JavaScript code. The code could be potentially executed later by another (possibly privileged) user.
CVE-2023-46281 1 Siemens 4 Opcenter Quality, Simatic Pcs Neo, Sinumerik Integrate Runmyhmi \/automotive and 1 more 2024-05-14 N/A 8.8 HIGH
A vulnerability has been identified in Opcenter Quality (All versions < V2312), SIMATIC PCS neo (All versions < V4.1), SINEC NMS (All versions < V2.0 SP1), Totally Integrated Automation Portal (TIA Portal) V14 (All versions), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 7), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 3). When accessing the UMC Web-UI from affected products, UMC uses an overly permissive CORS policy. This could allow an attacker to trick a legitimate user to trigger unwanted behavior.
CVE-2023-28766 1 Siemens 78 Siprotec 5 6md85, Siprotec 5 6md85 Firmware, Siprotec 5 6md86 and 75 more 2024-05-14 N/A 7.5 HIGH
A vulnerability has been identified in SIPROTEC 5 6MD85 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 6MD86 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 6MD89 (CP300) (All versions >= V7.80 < V9.64), SIPROTEC 5 6MU85 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7KE85 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7SA82 (CP100) (All versions), SIPROTEC 5 7SA82 (CP150) (All versions < V9.40), SIPROTEC 5 7SA86 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7SA87 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7SD82 (CP100) (All versions), SIPROTEC 5 7SD82 (CP150) (All versions < V9.40), SIPROTEC 5 7SD86 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7SD87 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7SJ81 (CP100) (All versions < V8.89), SIPROTEC 5 7SJ81 (CP150) (All versions < V9.40), SIPROTEC 5 7SJ82 (CP100) (All versions < V8.89), SIPROTEC 5 7SJ82 (CP150) (All versions < V9.40), SIPROTEC 5 7SJ85 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7SJ86 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7SK82 (CP100) (All versions < V8.89), SIPROTEC 5 7SK82 (CP150) (All versions < V9.40), SIPROTEC 5 7SK85 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7SL82 (CP100) (All versions), SIPROTEC 5 7SL82 (CP150) (All versions < V9.40), SIPROTEC 5 7SL86 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7SL87 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7SS85 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7ST85 (CP300) (All versions >= V7.80 < V9.64), SIPROTEC 5 7ST86 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7SX82 (CP150) (All versions < V9.40), SIPROTEC 5 7SX85 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7UM85 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7UT82 (CP100) (All versions), SIPROTEC 5 7UT82 (CP150) (All versions < V9.40), SIPROTEC 5 7UT85 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7UT86 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7UT87 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7VE85 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7VK87 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 7VU85 (CP300) (All versions >= V7.80 < V9.40), SIPROTEC 5 Communication Module ETH-BA-2EL (All versions < V9.40 installed on CP150 and CP300 devices), SIPROTEC 5 Communication Module ETH-BA-2EL (All versions < V8.89 installed on CP100 devices), SIPROTEC 5 Communication Module ETH-BB-2FO (All versions < V9.40 installed on CP150 and CP300 devices), SIPROTEC 5 Communication Module ETH-BB-2FO (All versions < V8.89 installed on CP100 devices), SIPROTEC 5 Communication Module ETH-BD-2FO (All versions < V9.40), SIPROTEC 5 Compact 7SX800 (CP050) (All versions < V9.40). Affected devices lack proper validation of http request parameters of the hosted web service. An unauthenticated remote attacker could send specially crafted packets that could cause denial of service condition of the target device.