CVE-2021-35527 1 Hitachienergy 1 Esoms 2023-05-16 5.0 MEDIUM 7.5 HIGH
Password autocomplete vulnerability in the web application password field of Hitachi ABB Power Grids eSOMS allows attacker to gain access to user credentials that are stored by the browser. This issue affects: Hitachi ABB Power Grids eSOMS version 6.3 and prior versions.
CVE-2019-19096 1 Hitachienergy 1 Esoms 2023-05-16 3.6 LOW 6.1 MEDIUM
The Redis data structure component used in ABB eSOMS versions 6.0 to 6.0.2 stores credentials in clear text. If an attacker has file system access, this can potentially compromise the credentials' confidentiality.
CVE-2019-19002 1 Hitachienergy 1 Esoms 2023-05-16 3.5 LOW 5.4 MEDIUM
For ABB eSOMS versions 4.0 to 6.0.2, the X-XSS-Protection HTTP response header is not set in responses from the web server. For older web browser not supporting Content Security Policy, this might increase the risk of Cross Site Scripting.
CVE-2019-19000 1 Hitachienergy 1 Esoms 2023-05-16 6.4 MEDIUM 6.5 MEDIUM
For ABB eSOMS 4.0 to 6.0.3, the Cache-Control and Pragma HTTP header(s) have not been properly configured within the application response. This can potentially allow browsers and proxies to cache sensitive information.
CVE-2018-14805 1 Hitachienergy 1 Esoms 2023-05-16 7.5 HIGH 9.8 CRITICAL
ABB eSOMS version 6.0.2 may allow unauthorized access to the system when LDAP is set to allow anonymous authentication, and specific key values within the eSOMS web.config file are present. Both conditions are required to exploit this vulnerability.
CVE-2021-27414 1 Hitachienergy 1 Ellipse Enterprise Asset Management 2023-05-16 4.3 MEDIUM 6.1 MEDIUM
An attacker could trick a user of Hitachi ABB Power Grids Ellipse Enterprise Asset Management (EAM) versions prior to and including 9.0.25 into visiting a malicious website posing as a login page for the Ellipse application and gather authentication credentials.
CVE-2021-27416 1 Hitachienergy 1 Ellipse Enterprise Asset Management 2023-05-16 5.8 MEDIUM 5.4 MEDIUM
An attacker could exploit this vulnerability in Hitachi ABB Power Grids Ellipse Enterprise Asset Management (EAM) versions prior to and including 9.0.25 by tricking a user to click on a link containing malicious code that would then be run by the web browser. This can result in the compromise of confidential information, or even the takeover of the user’s session.
CVE-2017-16731 1 Hitachienergy 1 Ellipse 2023-05-16 2.9 LOW 8.8 HIGH
An Unprotected Transport of Credentials issue was discovered in ABB Ellipse 8.3 through Ellipse 8.9 released prior to December 2017 (including Ellipse Select). A vulnerability exists in the authentication of Ellipse to LDAP/AD using the LDAP protocol. An attacker could exploit the vulnerability by sniffing local network traffic, allowing the discovery of authentication credentials.
CVE-2021-35529 1 Hitachienergy 2 Counterparty Settlement And Billing, Retail Operations 2023-05-16 6.5 MEDIUM 7.2 HIGH
Insufficiently Protected Credentials vulnerability in client environment of Hitachi ABB Power Grids Retail Operations and Counterparty Settlement Billing (CSB) allows an attacker or unauthorized user to access database credentials, shut down the product and access or alter. This issue affects: Hitachi ABB Power Grids Retail Operations version 5.7.2 and prior versions. Hitachi ABB Power Grids Counterparty Settlement Billing (CSB) version 5.7.2 and prior versions.
CVE-2019-18998 1 Hitachienergy 1 Asset Suite 2023-05-16 5.5 MEDIUM 7.1 HIGH
Insufficient access control in the web interface of ABB Asset Suite versions 9.0 to 9.3, 9.4 prior to 9.4.2.6, 9.5 prior to 9.5.3.2 and 9.6.0 enables full access to directly referenced objects. An attacker with knowledge of a resource's URL can access the resource directly.
CVE-2021-40335 1 Hitachienergy 2 Modular Switchgear Monitoring, Modular Switchgear Monitoring Firmware 2023-04-19 N/A 8.8 HIGH
A vulnerability exists in the HTTP web interface where the web interface does not sufficiently verify if a well-formed, valid, consistent request was intentionally provided by the user who submitted the request. This cause a Cross Site Request Forgery (CSRF), which if exploited could lead an attacker to gain unauthorized access to the web application and perform an unwanted operation on it without the knowledge of the legitimate user. An attacker, who successfully makes an MSM user who has already established a session to MSM web interface clicks a forged link to the MSM web interface, e.g., link is sent per E-Mail, could perform harmful command on MSM through its web server interface. This issue affects: Hitachi Energy MSM V2.2 and prior versions.
CVE-2021-35532 1 Hitachienergy 2 Txpert Hub Coretec 4, Txpert Hub Coretec 4 Firmware 2023-04-19 7.2 HIGH 6.7 MEDIUM
A vulnerability exists in the file upload validation part of Hitachi Energy TXpert Hub CoreTec 4 product. The vulnerability allows an attacker or malicious agent who manages to gain access to the system and obtain an account with sufficient privilege to upload a malicious firmware to the product. This issue affects: Hitachi Energy TXpert Hub CoreTec 4 version 2.0.0; 2.0.1; 2.1.0; 2.1.1; 2.1.2; 2.1.3; 2.2.0; 2.2.1.
CVE-2021-35535 1 Hitachienergy 6 Relion 650, Relion 650 Firmware, Relion 670 and 3 more 2023-04-19 6.8 MEDIUM 8.1 HIGH
Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who manages to get access to the front network port and to cause a reboot sequences of the device may exploit the vulnerability, where there is a tiny time gap during the booting process where an older version of VxWorks is loaded prior to application firmware booting, could exploit the vulnerability in the older version of VxWorks and cause a denial-of-service on the product. This issue affects: Hitachi Energy Relion 670 Series 2.2.2 all revisions; 2.2.3 versions prior to 2.2.3.3. Hitachi Energy Relion 670/650 Series 2.2.0 all revisions; 2.2.4 all revisions. Hitachi Energy Relion 670/650/SAM600-IO 2.2.1 all revisions.
CVE-2021-35534 1 Hitachienergy 10 Gms600, Gms600 Firmware, Pwc600 and 7 more 2023-04-19 9.0 HIGH 7.2 HIGH
Insufficient security control vulnerability in internal database access mechanism of Hitachi Energy Relion 670/650/SAM600-IO, Relion 650, GMS600, PWC600 allows attacker who successfully exploited this vulnerability, of which the product does not sufficiently restrict access to an internal database tables, could allow anybody with user credentials to bypass security controls that is enforced by the product. Consequently, exploitation may lead to unauthorized modifications on data/firmware, and/or to permanently disabling the product. This issue affects: Hitachi Energy Relion 670 Series 2.0 all revisions; 2.2.2 all revisions; 2.2.3 versions prior to 2.2.3.5. Hitachi Energy Relion 670/650 Series 2.1 all revisions. 2.2.0 all revisions; 2.2.4 all revisions; Hitachi Energy Relion 670/650/SAM600-IO 2.2.1 all revisions; 2.2.5 versions prior to 2.2.5.2. Hitachi Energy Relion 650 1.0 all revisions. 1.1 all revisions; 1.2 all revisions; 1.3 versions prior to 1.3.0.8; Hitachi Energy GMS600 1.3.0; 1.3.0.1; 1.2.0. Hitachi Energy PWC600 1.0.1 version 1.0.1.4 and prior versions; 1.1.0 version 1.1.0.1 and prior versions.
CVE-2022-29922 1 Hitachienergy 2 Microscada X Sys600, Sys600 2022-10-05 N/A 7.5 HIGH
Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS600 product. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*
CVE-2022-29492 1 Hitachienergy 2 Microscada X Sys600, Sys600 2022-10-05 N/A 7.5 HIGH
Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*
CVE-2021-35528 1 Hitachienergy 2 Counterparty Settlements And Billing, Retail Operations 2022-04-25 3.6 LOW 7.1 HIGH
Improper Access Control vulnerability in the application authentication and authorization of Hitachi Energy Retail Operations, Counterparty Settlement and Billing (CSB) allows an attacker to execute a modified signed Java Applet JAR file. A successful exploitation may lead to data extraction or modification of data inside the application. This issue affects: Hitachi Energy Retail Operations 5.7.3 and prior versions. Hitachi Energy Counterparty Settlement and Billing (CSB) 5.7.3 prior versions.
CVE-2021-40334 1 Hitachienergy 4 Fox615, Fox615 Firmware, Xcm20 and 1 more 2021-12-08 5.0 MEDIUM 7.5 HIGH
Missing Handler vulnerability in the proprietary management protocol (port TCP 5558) of Hitachi Energy FOX61x, XCM20 allows an attacker that exploits the vulnerability by activating SSH on port TCP 5558 to cause disruption to the NMS and NE communication. This issue affects: Hitachi Energy FOX61x versions prior to R15A. Hitachi Energy XCM20 versions prior to R15A.
CVE-2021-40333 1 Hitachienergy 4 Fox615, Fox615 Firmware, Xcm20 and 1 more 2021-12-07 5.5 MEDIUM 7.1 HIGH
Weak Password Requirements vulnerability in Hitachi Energy FOX61x, XCM20 allows an attacker to gain unauthorized access to the Data Communication Network (DCN) routing configuration. This issue affects: Hitachi Energy FOX61x versions prior to R15A. Hitachi Energy XCM20 versions prior to R15A.