Vulnerabilities (CVE)

Filtered by vendor Rockwellautomation Subscribe
Total 241 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2023-27856 1 Rockwellautomation 1 Thinmanager 2023-11-07 N/A 7.5 HIGH
In affected versions, path traversal exists when processing a message of type 8 in Rockwell Automation's ThinManager ThinServer. An unauthenticated remote attacker can exploit this vulnerability to download arbitrary files on the disk drive where ThinServer.exe is installed.
CVE-2023-27855 1 Rockwellautomation 1 Thinmanager 2023-11-07 N/A 9.8 CRITICAL
In affected versions, a path traversal exists when processing a message in Rockwell Automation's ThinManager ThinServer. An unauthenticated remote attacker could potentially exploit this vulnerability to upload arbitrary files to any directory on the disk drive where ThinServer.exe is installed. The attacker could overwrite existing executable files with attacker-controlled, malicious contents, potentially causing remote code execution.
CVE-2023-0755 3 Ge, Ptc, Rockwellautomation 9 Digital Industrial Gateway Server, Kepware Server, Kepware Serverex and 6 more 2023-11-07 N/A 9.8 CRITICAL
The affected products are vulnerable to an improper validation of array index, which could allow an attacker to crash the server and remotely execute arbitrary code.
CVE-2023-0754 3 Ge, Ptc, Rockwellautomation 9 Digital Industrial Gateway Server, Kepware Server, Kepware Serverex and 6 more 2023-11-07 N/A 9.8 CRITICAL
The affected products are vulnerable to an integer overflow or wraparound, which could  allow an attacker to crash the server and remotely execute arbitrary code.
CVE-2023-0027 1 Rockwellautomation 1 Modbus Tcp Server Add On Instructions 2023-11-07 N/A 4.3 MEDIUM
Rockwell Automation Modbus TCP Server AOI prior to 2.04.00 is vulnerable to an unauthorized user sending a malformed message that could cause the controller to respond with a copy of the most recent response to the last valid request. If exploited, an unauthorized user could read the connected device’s Modbus TCP Server AOI information.
CVE-2022-46670 1 Rockwellautomation 10 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 7 more 2023-11-07 N/A 6.1 MEDIUM
Rockwell Automation was made aware of a vulnerability by a security researcher from Georgia Institute of Technology that the MicroLogix 1100 and 1400 controllers contain a vulnerability that may give an attacker the ability to accomplish remote code execution.  The vulnerability is an unauthenticated stored cross-site scripting vulnerability in the embedded webserver. The payload is transferred to the controller over SNMP and is rendered on the homepage of the embedded website.
CVE-2022-3752 1 Rockwellautomation 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more 2023-11-07 N/A 7.5 HIGH
An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation.
CVE-2022-3166 1 Rockwellautomation 4 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 1 more 2023-11-07 N/A 7.5 HIGH
Rockwell Automation was made aware that the webservers of the Micrologix 1100 and 1400 controllers contain a vulnerability that may lead to a denial-of-service condition. The security vulnerability could be exploited by an attacker with network access to the affected systems by sending TCP packets to webserver and closing it abruptly which would cause a denial-of-service condition for the web server application on the device
CVE-2022-3157 1 Rockwellautomation 12 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 9 more 2023-11-07 N/A 7.5 HIGH
A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS).
CVE-2022-3156 1 Rockwellautomation 1 Studio 5000 Logix Emulate 2023-11-07 N/A 7.8 HIGH
A remote code execution vulnerability exists in Rockwell Automation Studio 5000 Logix Emulate software.  Users are granted elevated permissions on certain product services when the software is installed. Due to this misconfiguration, a malicious user could potentially achieve remote code execution on the targeted software.
CVE-2022-38744 1 Rockwellautomation 1 Factorytalk Alarms And Events 2023-11-07 N/A 7.5 HIGH
An unauthenticated attacker with network access to a victim's Rockwell Automation FactoryTalk Alarm and Events service could open a connection, causing the service to fault and become unavailable. The affected port could be used as a server ping port and uses messages structured with XML.
CVE-2018-19615 1 Rockwellautomation 2 Powermonitor 1000, Powermonitor 1000 Firmware 2023-11-07 4.3 MEDIUM 6.1 MEDIUM
Rockwell Automation Allen-Bradley PowerMonitor 1000 all versions. A remote attacker could inject arbitrary code into a targeted user’s web browser to gain access to the affected device.
CVE-2023-29464 1 Rockwellautomation 1 Factorytalk Linx 2023-10-20 N/A 9.1 CRITICAL
FactoryTalk Linx, in the Rockwell Automation PanelView Plus, allows an unauthenticated threat actor to read data from memory via crafted malicious packets. Sending a size larger than the buffer size results in leakage of data from memory resulting in an information disclosure. If the size is large enough, it causes communications over the common industrial protocol to become unresponsive to any type of packet, resulting in a denial-of-service to FactoryTalk Linx over the common industrial protocol.
CVE-2023-2262 1 Rockwellautomation 66 1756-en2f Series A, 1756-en2f Series A Firmware, 1756-en2f Series B and 63 more 2023-09-22 N/A 9.8 CRITICAL
A buffer overflow vulnerability exists in the Rockwell Automation select 1756-EN* communication devices. If exploited, a threat actor could potentially leverage this vulnerability to perform a remote code execution. To exploit this vulnerability, a threat actor would have to send a maliciously crafted CIP request to device.
CVE-2023-29463 1 Rockwellautomation 1 Pavilion8 2023-09-15 N/A 5.4 MEDIUM
The JMX Console within the Rockwell Automation Pavilion8 is exposed to application users and does not require authentication. If exploited, a malicious user could potentially retrieve other application users’ session data and or log users out of their session.
CVE-2023-2071 1 Rockwellautomation 2 Factorytalk View, Panelview Plus 2023-09-14 N/A 9.8 CRITICAL
Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets.  The device has the functionality, through a CIP class, to execute exported functions from libraries.  There is a routine that restricts it to execute specific functions from two dynamic link library files.  By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.
CVE-2023-2917 1 Rockwellautomation 1 Thinmanager Thinserver 2023-08-23 N/A 9.8 CRITICAL
The Rockwell Automation Thinmanager Thinserver is impacted by an improper input validation vulnerability.  Due to an improper input validation, a path traversal vulnerability exists, via the filename field, when the ThinManager processes a certain function. If exploited, an unauthenticated remote attacker can upload arbitrary files to any directory on the disk drive where ThinServer.exe is installed.  A malicious user could exploit this vulnerability by sending a crafted synchronization protocol message and potentially gain remote code execution abilities.
CVE-2023-2915 1 Rockwellautomation 1 Thinmanager Thinserver 2023-08-23 N/A 9.1 CRITICAL
The Rockwell Automation Thinmanager Thinserver is impacted by an improper input validation vulnerability, Due to improper input validation, a path traversal vulnerability exists when the ThinManager software processes a certain function. If exploited, an unauthenticated remote threat actor can delete arbitrary files with system privileges. A malicious user could exploit this vulnerability by sending a specifically crafted synchronization protocol message resulting in a denial-of-service condition.
CVE-2023-2914 1 Rockwellautomation 1 Thinmanager Thinserver 2023-08-23 N/A 7.5 HIGH
The Rockwell Automation Thinmanager Thinserver is impacted by an improper input validation vulnerability, an integer overflow condition exists in the affected products. When the ThinManager processes incoming messages, a read access violation occurs and terminates the process. A malicious user could exploit this vulnerability by sending a crafted synchronization protocol message and causing a denial of service condition in the software.
CVE-2023-2423 1 Rockwellautomation 2 Armor Powerflex, Armor Powerflex Firmware 2023-08-15 N/A 7.5 HIGH
A vulnerability was discovered in the Rockwell Automation Armor PowerFlex device when the product sends communications to the local event log. Threat actors could exploit this vulnerability by sending an influx of network commands, causing the product to generate an influx of event log traffic at a high rate. If exploited, the product would stop normal operations and self-reset creating a denial-of-service condition. The error code would need to be cleared prior to resuming normal operations.