CVE-2023-4487 1 Ge 1 Cimplicity 2023-09-09 N/A 7.8 HIGH
GE CIMPLICITY 2023 is by a process control vulnerability, which could allow a local attacker to insert malicious configuration files in the expected web server execution path to escalate privileges and gain full control of the HMI software.
CVE-2023-3463 1 Ge 1 Cimplicity 2023-07-28 N/A 9.8 CRITICAL
All versions of GE Digital CIMPLICITY that are not adhering to SDG guidance and accepting documents from untrusted sources are vulnerable to memory corruption issues due to insufficient input validation, including issues such as out-of-bounds reads and writes, use-after-free, stack-based buffer overflows, uninitialized pointers, and a heap-based buffer overflow. Successful exploitation could allow an attacker to execute arbitrary code.
CVE-2021-27452 1 Ge 2 Mu320e, Mu320e Firmware 2023-05-05 7.2 HIGH 7.8 HIGH
The software contains a hard-coded password that could allow an attacker to take control of the merging unit using these hard-coded credentials on the MU320E (all firmware versions prior to v04A00.1).
CVE-2023-1552 1 Ge 1 Toolboxst 2023-04-20 N/A 7.8 HIGH
ToolboxST prior to version 7.10 is affected by a deserialization vulnerability. An attacker with local access to an HMI or who has conducted a social engineering attack on an authorized operator could execute code in a Toolbox user's context through the deserialization of an untrusted configuration file. Two CVSS scores have been provided to capture the differences between the two aforementioned attack vectors.  Customers are advised to update to ToolboxST 7.10 which can be found in ControlST 7.10. If unable to update at this time customers should ensure they are following the guidance laid out in GE Gas Power's Secure Deployment Guide (GEH-6839). Customers should ensure they are not running ToolboxST as an Administrative user. 
CVE-2022-2848 4 Ge, Ptc, Rockwellautomation and 1 more 8 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 5 more 2023-04-20 N/A 9.1 CRITICAL
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a heap-based buffer. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-16486.
CVE-2022-2825 4 Ge, Ptc, Rockwellautomation and 1 more 8 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 5 more 2023-04-20 N/A 9.8 CRITICAL
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a stack-based buffer. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-18411.
CVE-2020-16242 1 Ge 4 S2020, S2020 Firmware, S2024 and 1 more 2023-01-31 4.3 MEDIUM 6.1 MEDIUM
The affected Reason S20 Ethernet Switch is vulnerable to cross-site scripting (XSS), which may allow an attacker to trick application users into performing critical application actions that include, but are not limited to, adding and updating accounts.
CVE-2019-6564 1 Ge 1 Ge Communicator 2023-01-31 6.9 MEDIUM 7.8 HIGH
GE Communicator, all versions prior to 4.0.517, allows a non-administrative user to place malicious files within the installer file directory, which may allow an attacker to gain administrative privileges on a system during installation or upgrade.
CVE-2022-43975 1 Ge 2 Ms 3000, Ms 3000 Firmware 2023-01-30 N/A 7.5 HIGH
An issue was discovered in FC46-WebBridge on GE Grid Solutions MS3000 devices before 3.7.6.25p0_3.2.2.17p0_4.7p0. A vulnerability in the web server allows arbitrary files and configurations to be read via directory traversal over TCP port 8888.
CVE-2022-43977 1 Ge 2 Ms 3000, Ms 3000 Firmware 2023-01-26 N/A 9.8 CRITICAL
An issue was discovered on GE Grid Solutions MS3000 devices before 3.7.6.25p0_3.2.2.17p0_4.7p0. The debug port accessible via TCP (a qconn service) lacks access control.
CVE-2022-43976 1 Ge 2 Ms 3000, Ms 3000 Firmware 2023-01-26 N/A 9.8 CRITICAL
An issue was discovered in FC46-WebBridge on GE Grid Solutions MS3000 devices before 3.7.6.25p0_3.2.2.17p0_4.7p0. Direct access to the API is possible on TCP port 8888 via programs located in the cgi-bin folder without any authentication.
CVE-2022-24116 1 Ge 16 Inet 900, Inet 900 Firmware, Inet Ii 900 and 13 more 2023-01-05 N/A 9.8 CRITICAL
Certain General Electric Renewable Energy products have inadequate encryption strength. This affects iNET and iNET II before 8.3.0.
CVE-2022-24117 1 Ge 16 Inet 900, Inet 900 Firmware, Inet Ii 900 and 13 more 2023-01-05 N/A 9.8 CRITICAL
Certain General Electric Renewable Energy products download firmware without an integrity check. This affects iNET and iNET II before 8.3.0, SD before 6.4.7, TD220X before 2.0.16, and TD220MAX before 1.2.6.
CVE-2022-24118 1 Ge 16 Inet 900, Inet 900 Firmware, Inet Ii 900 and 13 more 2023-01-05 N/A 9.1 CRITICAL
Certain General Electric Renewable Energy products allow attackers to use a code to trigger a reboot into the factory default configuration. This affects iNET and iNET II before 8.3.0, SD before 6.4.7, TD220X before 2.0.16, and TD220MAX before 1.2.6.
CVE-2022-24119 1 Ge 16 Inet 900, Inet 900 Firmware, Inet Ii 900 and 13 more 2023-01-05 N/A 9.8 CRITICAL
Certain General Electric Renewable Energy products have a hidden feature for unauthenticated remote access to the device configuration shell. This affects iNET and iNET II before 8.3.0.
CVE-2022-24120 1 Ge 16 Inet 900, Inet 900 Firmware, Inet Ii 900 and 13 more 2023-01-05 N/A 4.6 MEDIUM
Certain General Electric Renewable Energy products store cleartext credentials in flash memory. This affects iNET and iNET II before 8.3.0.
CVE-2019-6548 1 Ge 1 Ge Communicator 2022-11-30 6.8 MEDIUM 9.8 CRITICAL
GE Communicator, all versions prior to 4.0.517, contains two backdoor accounts with hardcoded credentials, which may allow control over the database. This service is inaccessible to attackers if Windows default firewall settings are used by the end user.
CVE-2019-6546 1 Ge 1 Ge Communicator 2022-11-30 6.8 MEDIUM 7.8 HIGH
GE Communicator, all versions prior to 4.0.517, allows an attacker to place malicious files within the working directory of the program, which may allow an attacker to manipulate widgets and UI elements.
CVE-2021-27422 1 Ge 38 Multilin B30, Multilin B30 Firmware, Multilin B90 and 35 more 2022-10-24 5.0 MEDIUM 7.5 HIGH
GE UR firmware versions prior to version 8.1x web server interface is supported on UR over HTTP protocol. It allows sensitive information exposure without authentication.
CVE-2020-25193 1 Ge 6 Rt430, Rt430 Firmware, Rt431 and 3 more 2022-10-21 5.0 MEDIUM 5.3 MEDIUM
By having access to the hard-coded cryptographic key for GE Reason RT430, RT431 & RT434 GNSS clocks in firmware versions prior to version 08A06, attackers would be able to intercept and decrypt encrypted traffic through an HTTPS connection.