CVE-2022-4608

A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
Configurations

Configuration 1 (hide)

AND
OR cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.1:*:*:*:*:*:*:*
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.2:*:*:*:*:*:*:*
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.3:*:*:*:*:*:*:*
cpe:2.3:o:hitachienergy:rtu500_firmware:13.4.1:*:*:*:*:*:*:*
cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:*

History

No history.

Information

Published : 2023-07-26 06:15

Updated : 2023-08-03 14:51


NVD link : CVE-2022-4608

Mitre link : CVE-2022-4608

CVE.ORG link : CVE-2022-4608


JSON object : View

Products Affected

hitachienergy

  • rtu500_firmware
  • rtu500
CWE
CWE-787

Out-of-bounds Write

CWE-120

Buffer Copy without Checking Size of Input ('Classic Buffer Overflow')