Hirschmann OS2, RSP, and RSPE devices before HiOS 08.3.00 allow a denial of service. An unauthenticated, adjacent attacker can cause an infinite loop on one of the HSR ring ports of the device. This effectively breaks the redundancy of the HSR ring. If the attacker can perform the same attack on a second device, the ring is broken into two parts (thus disrupting communication between devices in the different parts).
                
            References
                    | Link | Resource | 
|---|---|
| https://www.belden.com/dfsmedia/f1e38517e0cd4caa8b1acb6619890f5e/12276-source/options/view | Vendor Advisory | 
| https://www.belden.com/security | Vendor Advisory | 
Configurations
                    Configuration 1 (hide)
            
            
  | 
    
History
                    No history.
Information
                Published : 2021-02-11 21:15
Updated : 2021-02-23 18:53
NVD link : CVE-2020-9307
Mitre link : CVE-2020-9307
CVE.ORG link : CVE-2020-9307
JSON object : View
Products Affected
                belden
- hirschmann_hios
 
CWE
                
                    
                        
                        CWE-835
                        
            Loop with Unreachable Exit Condition ('Infinite Loop')